Flame Retardant Zero Halogen Crosslinked Thermoset Single Core X-HF-
110 Flexible Power Cable, 0.6/1kV

Application

These power cables are mainly for use in fixed applications.

Standard

  • AS 5000.1
  • AS1125
  • AS3808

Cable Construction

CONDUCTOR Nominal 0 .2mm stranded flexible plain copper wire to AS 1125
INSULATION X-HF-110 to AS3808
COLOURS: Black, Red, Blue, White, Green/Yellow

Technical Characteristics

Flame Retardant Zero Halogen Crosslinked Thermoset Single Core X-HF-  110 Flexible Power Cable

CONDUCTOR SIZE MM2 ELECTRICAL
RESISTANCE
@20.C
CURRENT RAT`ING' AMPS 2 SINGLE CORES VOLTAGE DROP MV 1AM AT MAX OPERATING TEMPERATURE
MM2 OHM/KM SINGLE PHASE THREE PHASE
0.5 39 7 125 107
1.0 19.500 25 57.4 49.70
1.5 13.300 32 36.85 31 .90
2.5 7.980 45 20.1 17.40
4.0 4.950 59 12.5 10.80
6.0 3.300 75 8.35 7.23
10 1.910 105 4.97 4.30
16 1.210 135 3.13 2.71
25 0.780 185 1.99 1.72
35 0.554 225 1.44 1.25
50 0.386 275 1.07 0.929
70 0.272 350 0.769 0.657
95 0.206 435 0.567 0.491
120 0.161 510 0.465 0.403

Cable Parameter

CONDUCTOR SIZE NO.OF CORES CONDUCTOR NO./ OD NOMINAL
INSULATION THICKNESS
NOMINAL O.D. APPROX.CABLE
WEIGHT
MM2   MM MM MM KG/100M
0.5 1 16/0.2 0.7 2.40 1.10
1.0 1 32/0.2 0.7 2.80 1.50
1.5 1 30/0.25 0.7 3.10 2.00
2.5 1 50/0.25 0.7 3.60 2.90
4.0 1 12810.2 0.7 4.20 4.40
6.0 1 19210.2 0.7 4.80 6.60
10 1 32210.2 0.7 5.80 10.50
16 1 511/0.2 0.7 6.90 16.10
25 1 78410.2 0.9 8.70 28.80
35 1 1120/0.2 0.9 9.60 36.30
50 1 1568/0.2 1.0 11.20 49.50
70 1 2240/0.2 1.1 13.20 70.10
95 1 3040/0.2 1.1 15.00 94.20
120 1 3800/0.2 1.2 16.70 116.80